MES-U ElectrodeSteam HumidifiersInstallation, Operation,Maintenance, Spare Parts, andExploded Views GuideIMPORTANT: Read and save this guide for futur
-8-MES-U INTERNAL AND FIELD WIRINGWIRING DIAGRAM number 150-6240 REV. B(For PVC or LVC unit with remote or attached electrical)STEAM CYLINDERNOTE: SOL
LIMITED WARRANTYNORTEC INDUSTRIES INCORPORATED and/or NORTEC AIRCONDITIONING INDUSTRIES LIMITED (hereinafter collectively referred to as THECOMPANY),
Model # :_________________________Serial # :_________________________Cylinder # :_______________________Cylinder Last Replaced:_______________________
Table of ContentsINSTALLATION 1–RECEIVING EQUIPMENT...1–PRINCIPAL OF OPERATION ...1–WATER SUPPLY A
INSTALLATIONRECEIVING EQUIPMENT1. Check packing slip to ensure ALL material hasbeen received.2. Inspect box for damage and note on shippingwaybill acc
WATER SUPPLY AND PLUMBING1. The orifice in the fill valve is sized for an extendedwater pressure range of 30 to 85 psi.2. For water pressure between 1
out and the fill solenoid will again open until thecylinder is again full.This cycling of the red light and fill valve willcontinue until the unit’s f
2. The old cylinder must be drained completelybefore removing. This is done by pushing the autoon/off/drain switch to the “drain” position.3. When com
is normally caused by short cycling, a restricted drain,or back pressure. The foam, generated in theseinstances, is conductive and may lead to false f
Red “Change Cylinder” light on - Water NOT at top ofcylinder:Water foaming to top of cylinder causing false fullcylinder indication. This also may be
-7-MES-U/MES-P HUMIDIFIERPHYSICAL DATAMESU DIM 10/19/98WEIGHTS (DRY)DIMENSIONSNOTES:1. FOR HEIGHT OF 5 LB PVC USE HEIGHT OF 10 LB MODEL.2. PVC = PRIMA