MES ElectrodeSteam HumidifiersInstallation, Operation,Maintenance, Spare Parts, andExploded Views GuideIMPORTANT: Read and save this guide for future
Software requirements for Modbus RTUModbus addresses:4XXXX – R/W3XXXX - RCommand Description MODBUSaddressDetailsOutput ControlOFFDisables thehumidifi
-9-Set MODBUSparity *Change the humidifier controller’sMODBUS parity.Range is None, Even, OddThis setting shall be non-volatile with adefault setting
-10-MaximumproductionThe rated maximum steam productionfor the humidifier30802ValuewrittenintoUnittype(40600) is also stored hereAlarms The humidifier
-11-MES-U/MES-P HUMIDIFIERPHYSICAL DATAMESU DIM 10/19/98WEIGHTS (DRY)DIMENSIONSNOTES:1. FOR HEIGHT OF 5 LB PVC USE HEIGHT OF 10 LB MODEL.2. PVC = PRIM
-12-MES-U INTERNAL AND FIELD WIRINGWIRING DIAGRAM number 150-6240 REV. B(For PVC or LVC unit with remote or attached electrical)STEAM CYLINDERNOTE: SO
- 13-
- -14-POS.DESCRIPTIONCommentsNORTEC208/380/208/380/208/380/208/380/NOPA RT230/460/230V460/230V460/230V460/NUMBER277V575V575V575V575V1Cylinder - To ord
LIMITED WARRANTYWalter Meier Inc. and/or Walter Meier Ltd. (hereinafter collectively referred to asTHE COMPANY), warrant for a period of two years fro
Table of ContentsINSTALLATION 1RECEIVING EQUIPMENT ...1PRINCIPAL OF OPERATION ...
Walter Meier (Climate USA) Inc.826 Proctor Avenue, Ogdensburg, New York 13669Walter Meier (Climate Canada) Ltd.2740 Fenton Road, Ottawa, Ontario K1T3T
INSTALLATIONRECEIVING EQUIPMENT1. Check packing slip to ensure ALL material hasbeen received.2. Inspect box for damage and note on shippingwaybill acc
WATER SUPPLY AND PLUMBING1. The fill valve is sized for an extended waterpressure range of 30 to 80 psi.2. For cases below 15 psi add a pressure boost
The red light simply acts as a safety to shut off thefill valve and prevent over-filling. With the red light on,the water in the cylinder will continu
dependent on water supply conditions and humidifierusage. Failure to replace the cylinder at the end ofcylinder life may result in unit damage. NORTEC
FOAMING: The phenomenon which can occur inwater when the impurities, already in the water reachan excess concentration as a result of boiling awaypure
Water remains at high level and won’t concentrate:This is normal on cold start-up and can beaccelerated by adding maximum 1/2 tsp. of dissolvedsalt to
DIAGNOSTIC PROCEDURES - TROUBLESHOOTING GUIDEUnit Status LampSymptom Corrective actionsYellow GreenOn On Maximum water levelinside cylinder.This usual